These cables are indicated for executing permanent installations where low fumes and corrosive gas emission is required in the event of fire, such as public premises, hospitals, schools, shopping centres and airports. Electrical conductors of different colours and sections required to execute each installation are inserted onto the inside of a corrugated tube, thus achieving a product that provides the installer with an integral service that has numerous advantages and also saves time and costs.
Applications
Individual by-pass
Indoor or receiver installations
Public premises
Installations in premises with fire or explosion risk
Appropriate for installations where increased fire protection is required
Flexible electrolytic copper conductor (Class V) according to BS EN 60228:2005 (previously BS6360)and UNE 60228.
2. Insulation
Thermoplastic polyolefin insulation, type TI-7, according to UNE 211002 and HD 21.15S1:2006. With special properties against flame propagation, fire, opacity of fumes and corrosiveness of gases.
3. Tube
Tube, Corrugated fireproof polypropylene tube, with low halogen content, low fumes emission and non-flame propagating. Resistant to acids, bases and organic solvents and excellent compression properties (750N).
Rated voltage
450/750V
Test voltage
2.500V in A.C.
Maximum temperature
70ºC
Other characteristics
Colours according to UNE 21031 and HD 21.1S4:2002
Non-flame propagating according to UNE-EN 60332, EN 60332 and IEC 60332
Non-fire propagating UNE-EN 50266-2-4 and EN 50266
Low halogen content according to UNE 211002 Appendix A and HD 21.15S1:2006
Low opaque smoke emission according to UNE-EN 61034, EN 61034 and IEC 61034
Low corrosive gas emission according to UNE 211002 Appendix A and HD