H05Z1-K Print E-mail

Description

H05Z1-K

H05Z1-K.jpg

 

Description


These flexible and halogen-free cables are indicated for permanent installations in public premises and where low fumes and corrosive gas emission is required in case of fire.

Applications


- Individual by-pass
- Indoor or receiver installations
- Public premises
- Installations in premises with fire or explosion risk
- Appropriate for other installations where greater fire protection is required, even in housing.

 

 

domestico.gif industrial.gif
th_rosh

 

Technical Characteristics

H05Z1-K

 

 

 

ES05Z1.jpg ES05Z1detalle.jpg

 


1. Conductor

Flexible electrolytic copper conductor (Class V) according to BS EN 60228:2005 (previously BS6360) and UNE 60228.

2. Insulation

Thermoplastic halogen-free material insulation, type TI-7, according to HD 21.15S1:2006.

Rated voltage

300/500V

Test voltage

2.000V in A.C.

Maximum temperature

70ºC

Other characteristics

  • Colours according to UNE 21031 and HD 21.1S4:2002
  • Non-flame propagating according to UNE-EN 60332, EN 60332, IEC 60332
  • Low halogen content according to UNE-EN 21031-15 Appendix A and HD 21.15S1:2006
  • Low corrosive gas emission according to UNE 21031 Appendix A0, HD 21.15S1:2006
  • Low opaque smoke emission according to UNE-EN 61034, EN 61034, IEC 61034

National norm / european

EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034
International norm
IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

 

Dimensions

H05Z1-K

 

Section

(mm2)

Resistance at 20ºC (Ω/Km)

External Diameter (mm)

Weight (kg/km)

0,50

39,00

2,10

9

0,75

26,00

2,30

11

1

19,50

2,80

14

 

Documents

H05Z1-K

 


pdflogo2.jpg